USA
Catalog   /   Home & Renovation   /   Autonomous Power Supply   /   UPS

Comparison SVC VP-1250-LCD 1250 VA vs RITAR RTM1200 Proxima-D 1200 VA

Add to comparison
SVC VP-1250-LCD 1250 VA
RITAR RTM1200 Proxima-D 1200 VA
SVC VP-1250-LCD 1250 VARITAR RTM1200 Proxima-D 1200 VA
Outdated Product
from $103.68
Outdated Product
TOP sellers
Typesmartsmart
Form factorstandard (Tower)standard (Tower)
Switching to battery6 ms10 ms
Input
Input voltage1 phase (230V)1 phase (230V)
Input voltage range145 – 290 V175-265 V
Max. current6 А4 А
Bypass (direct connection)autoauto
Output
Output voltage1 phase (230V)1 phase (230V)
Peak output power1250 VA1200 VA
Rated output power750 W720 W
Output waveformpure sine wave (PSW)similar to a sinusoid (approximated)
Output frequency50/60 Hz50-60 Hz
Redundant sockets22
Non-redundant sockets1
Socket typetype F (Schuko)type F (Schuko)
No reserve C13/C14 connectors1
Battery
Total battery capacity7.5 Ah7 Ah
Number of batteries22
Battery typeGEL ( filled with gel)
Full charge time360 min
Cold start
Protection
Protection
short circuit protection
overload protection
noise filtering
data line protection
sound alarm
short circuit protection
overload protection
noise filtering
 
sound alarm
Fusemeltingmelting
Control interfaces
USB
 
General
Screen
Operating temperature0 – 40 °C0 – 40 °C
Dimensions (HxWxD)192x122x330 mm188x120x350 mm
Weight8.3 kg10.2 kg
Added to E-Catalogoctober 2021june 2016

Switching to battery

The time required to transfer the load from mains power to battery power. In standby and interactive UPSs (see Type), a short-term power failure occurs at this moment — accordingly, the shorter the time to switch to the battery, the more uniform the power supply is provided by the source during a power failure. Ideally, the switching time for the traditional 50 Hz AC frequency should be less than 5 ms (a quarter of one cycle of the sine wave). With inverter UPSs, the transfer time is, by definition, zero.

Input voltage range

In this case, the input voltage range is implied, in which the UPS is able to supply a stable voltage to the load only due to its own regulators, without switching to the battery. For redundant UPSs (see "Type") this range is quite small, approximately 190 to 260 V; for interactive and especially inverter ones, it is much wider. Some UPS models allow you to manually set the input voltage range.

Max. current

The maximum current drawn by the UPS. In fact, the current reaches its maximum value only when the UPS is operating from the mains with maximum load power and a completely discharged battery. However, when calculating the load on the power grid, this parameter should be taken into account.

Peak output power

The maximum output power supplied by the UPS, in other words, the highest apparent load power allowed for this model.

This indicator is measured in volt-amperes (the general meaning of this unit is the same as that of the watt, and different names are used to separate different types of power). The total power consumption of the load, implied in this case, is the sum of two powers — active and reactive. Active power is actually effective power (it is indicated in watts in the characteristics of electrical appliances). Reactive power is the power wasted by coils and capacitors in AC devices; with numerous coils and/or capacitors, this power can be a fairly significant part of the total energy consumption. Note that for simple tasks, you can use data on effective power (it is often given for UPS — see below); but for accurate electrical calculations it is worth using the full one.

The simplest selection rule for this indicator is: the maximum output power of the UPS in volt-amperes should be at least 1.7 times higher than the total load power in watts. There are also more detailed calculation formulas that take into account the characteristics of different types of load; they can be found in special sources. As for specific values, the most modest modern UPSs give out 700 – 1000 VA, or even less — this is enough to power a PC of average performance; and in the most "heavyweight" models, th...is figure can be 8 – 10 kVA and higher.

Rated output power

The effective output power of the UPS is, in fact, the maximum active power of the load that can be connected to the device.

Active power is consumed directly for the operation of the device; it is expressed in watts. In addition to it, most AC devices also consume reactive power, which is "wasted" (relatively speaking) is spent by coils and capacitors. Apparent power (denoted in volt-amperes) is precisely the sum of active and reactive power; it is this characteristic that should be used in accurate electrical calculations. See "Maximum output power" for details; here we note that when selecting a UPS for a relatively simple application, it is quite possible to use only effective power. This is at least easier than converting the watts claimed in the characteristics of the connected devices into full power volt-amps.

The most modest modern "uninterruptibles" give out less than 500 watts. 501 – 1000 W can be considered an average value, 1.1 – 2 kW is above average, and in the most powerful models this figure exceeds 2 kW and can reach very impressive values (up to 1000 kW or more in some industrial class UPS).

Output waveform

The form of a graph describing the changes in voltage at the output of the UPS.

Pure sinewave. The classic AC voltage graph, this is how it changes in an AC network; The sine wave output means that the UPS has little to no distortion compared to the mains. As a result, such power is suitable for any AC technology, and some devices (for example, audio equipment) generally require an exceptionally pure sine wave. However, this requires rather complex technical solutions, and therefore this waveform can be found in expensive interactive and inverter UPSs.

Simulated sine wave (approximated). This signal has a shape close to a sinusoid, but the graph line in this case is not smooth, but consists of separate rectangular “steps”. This waveform is provided by most inexpensive UPSs; such devices are inexpensive and quite suitable for powering computer equipment.

Output frequency

The frequency (frequency range) of the AC voltage output by the UPS. For computer technology, the frequency range of 47-53 Hz is considered normal, although the smaller the deviation from the 50 Hz standard, the better. On the other hand, in some UPS models, this frequency can be automatically synchronized with the frequency of the mains — so the power supplied to the load will not differ regardless of whether the load is powered by the mains or from the battery. In this case, a wider frequency range, on the contrary, is more desirable.

Non-redundant sockets

The number of outlets without connection to the power reserve provided in the design of the UPS. For devices connected to such outlets, the UPS only performs the function of a surge protector — it smooths out small voltage irregularities; when the mains voltage fails, the power to these outlets is also turned off. The sockets have a standard shape and are compatible with the vast majority of popular 230 V plugs. The presence of sockets without a reserve allows you to connect equipment with different requirements for uninterrupted power supply to one UPS. For example, sockets with a reserve (see above) can include a system unit and a monitor, and a printer can be connected to a socket without a reserve. Thus, if the mains power fails, the computer will continue to work, allowing you to save data, and the printer will turn off, thus saving battery power and providing longer UPS runtime.

No reserve C13/C14 connectors

The number of C13 / C14 connectors without connection to the power reserve, provided in the design of the UPS.

Unlike connectors with a reserve, such connectors do not protect against loss of voltage in the network — for devices connected to them, the UPS only works as a surge protector, smoothing out power surges. This allows you to connect to the UPS devices that do not require continuous power and are not afraid of shutdowns, such as speakers or printers. In the event of a power failure, such devices will not consume battery power, and the UPS will be able to power devices for which continuous power, on the contrary, is essential for longer.

The C13/C14 connector is known colloquially as a "computer socket"; it delivers the same 230 V as a regular household outlet, but is not compatible with conventional plugs, as uses three flat contacts. However, there are adapters between these standards.