Comparison APC Easy-UPS BV 1000VA BV1000I-GR 1000 VA vs CyberPower BU1000E 1000 VA

Add to comparison
APC Easy-UPS BV 1000VA BV1000I-GR 1000 VA
CyberPower BU1000E 1000 VA
APC Easy-UPS BV 1000VA BV1000I-GR 1000 VACyberPower BU1000E 1000 VA
Outdated ProductOutdated Product
TOP sellers
Main
Interactive UPS. Cold start. Quiet work.
Typesmartsmart
Form factorregular (extension)regular (extension)
Switching to battery6 ms4 ms
Input
Input voltage1 phase (230V)1 phase (230V)
Input voltage range170 – 280 V165-280 V
Max. current7 A5 A
Input frequency45 – 65 Hz45-65 Hz
Bypass (direct connection)is absentis absent
Output
Output voltage1 phase (230V)1 phase (230V)
Max. output power1000 VA1000 VA
Rated output power600 W600 W
Output voltage distortion10 %
Efficiency97.4 %
Output waveformsimilar to a sinusoid (approximated)similar to a sinusoid (approximated)
Output frequency49 – 61 Hz50-60 Hz
Redundant sockets44
Socket typetype F (Schuko)type F (Schuko)
Battery
Battery typelead acid
Supplied battery(s) capacity9 Ah4.5 Ah
Batteries12
Full charge time480 min480 min
Cold start
Protection
Protection
short circuit protection
overload protection
noise filtering
sound alarm
short circuit protection
overload protection
noise filtering
sound alarm
Fuseautoauto
Surge protection125 J
General
Operating temperature0 – 40 °C0 – 40 °C
Noise level40 dB40 dB
Dimensions (HxWxD)92x305x160 mm111x290x190 mm
Weight5.7 kg6.9 kg
Added to E-Catalogjuly 2018september 2016

Switching to battery

The time required to transfer the load from mains power to battery power. In standby and interactive UPSs (see Type), a short-term power failure occurs at this moment — accordingly, the shorter the time to switch to the battery, the more uniform the power supply is provided by the source during a power failure. Ideally, the switching time for the traditional 50 Hz AC frequency should be less than 5 ms (a quarter of one cycle of the sine wave). With inverter UPSs, the transfer time is, by definition, zero.

Input voltage range

In this case, the input voltage range is implied, in which the UPS is able to supply a stable voltage to the load only due to its own regulators, without switching to the battery. For redundant UPSs (see "Type") this range is quite small, approximately 190 to 260 V; for interactive and especially inverter ones, it is much wider. Some UPS models allow you to manually set the input voltage range.

Max. current

The maximum current drawn by the UPS. In fact, the current reaches its maximum value only when the UPS is operating from the mains with maximum load power and a completely discharged battery. However, when calculating the load on the power grid, this parameter should be taken into account.

Input frequency

The operating frequency of the alternating current supplied to the input of the UPS — or more precisely, the frequency range of this current in which the device can supply the required power to the load due to its own regulators, without using a battery. When this range is exceeded, the UPS switches to battery mode. The smallest input voltage range is reserved for standby UPSs (see "Type"), the largest for inverter UPSs.

Output voltage distortion

This parameter characterizes the degree of difference between the AC voltage at the output of the UPS and the perfect voltage, the graph of which has the shape of a regular sinusoid. The perfect voltage is so named because it is the most uniform and creates the least unnecessary load on the connected devices. Thus, the distortion of the output voltage is one of the most important parameters that determine the quality of the power received by the load. A distortion level of 0% means that the UPS produces a perfect sine wave, up to 5% — slight sine wave distortion, up to 18% — strong distortion, from 18% to 40% — a trapezoidal signal, more than 40% — a square wave.

Efficiency

Efficiency (coefficient of performance) in the case of a UPS is the ratio of its output power to the power consumed from the network. This is one of the main parameters that determine the overall efficiency of the device: the higher the efficiency, the less energy the UPS wastes (due to heating parts, electromagnetic radiation, etc.). In modern models, the efficiency value can reach 99%.

Output frequency

The frequency (frequency range) of the AC voltage output by the UPS. For computer technology, the frequency range of 47-53 Hz is considered normal, although the smaller the deviation from the 50 Hz standard, the better. On the other hand, in some UPS models, this frequency can be automatically synchronized with the frequency of the mains — so the power supplied to the load will not differ regardless of whether the load is powered by the mains or from the battery. In this case, a wider frequency range, on the contrary, is more desirable.

Battery type

- Lead acid. Structurally, lead-acid batteries are based on a combination of electrodes made of lead compounds immersed in a liquid electrolyte, the role of which is played by an aqueous solution of sulfuric acid. The advantages of this type are simplicity and low cost, low self-discharge, no "memory effect" and maintaining performance in a wide temperature range. At the same time, the less charge remains in such batteries, the less current they produce. Also, lead-acid batteries are afraid of deep discharges, take a long time to charge, have large dimensions and weight in the context of other types.

- Lead-acid (AGM). An advanced type of lead-acid battery with an electrolyte in a jelly-like state. The gel electrolyte provides maximum contact with the negative and positive plates while maintaining a uniform consistency throughout the volume. AGM batteries impress with their high reliability, low self-discharge, deep discharge resistance and long service life. However, they are sensitive to charge quality, short circuits and negative temperatures.

— Li-Ion. Lithium-ion batteries have a high capacity with small dimensions and weight. They are not subject to the “memory effect”, they are able to charge quite quickly, they can boast of an excellent reserve for charge-discharge cycles. Li-Ion batteries also have disadvantages - first of all, it is sensitivity to low or high temperatures, and when overloaded, such a battery can catch fire or even explode. Howeve...r, due to the use of embedded controllers, the likelihood of such "accidents" is extremely small and, in general, the advantages of this technology significantly outweigh the disadvantages.

Supplied battery(s) capacity

The capacity of the battery installed in the UPS. For models with multiple batteries, this is both the total working capacity and the capacity of each individual battery: the batteries in such devices are usually connected in series, so that their total capacity corresponds to the capacity of each individual cell.

Theoretically, a higher battery capacity means the ability to power loads of a given capacity for longer. However, in fact, this parameter is more of a reference than practically significant. The fact is that the actual amount of energy stored by the battery depends not only on the capacity in amp-hours, but also on the voltage in volts; this voltage is often not specified in the characteristics, despite the fact that for accurate calculations it must be known. So when choosing, you should focus on more "close to life" characteristics — first of all, on the directly claimed operating time in different modes (see above).