USA
Catalog   /   Climate, Heating, Water Heating   /   Heating & Boilers   /   Boilers

Comparison BAXI Eco Four 24 F 24 kW
230 V
vs BAXI Main Digit 240 Fi 24 kW
230 V

Add to comparison
BAXI Eco Four 24 F 24 kW 230 V
BAXI Main Digit 240 Fi 24 kW 230 V
BAXI Eco Four 24 F 24 kW
230 V
BAXI Main Digit 240 Fi 24 kW
230 V
from $611.52 up to $796.68
Outdated Product
from $734.00
Outdated Product
TOP sellers
Energy sourcegasgas
Installationwallwall
Typedual-circuit (heating and DHW)dual-circuit (heating and DHW)
Heating area180 m²180 m²
Technical specs
Heat output24 kW24 kW
Min. heat output9.3 kW
Power supply230 V230 V
Power consumption130 W170 W
Coolant min. T30 °С30 °С
Coolant max. T85 °С85 °С
DHW circuit max. pressure8 bar8 bar
Consumer specs
DHW min. T35 °С35 °С
DHW max. T60 °С55 °С
Performance (ΔT=25°C)13.7 L/min13.7 L/min
Performance (ΔT ~30 °C)9.4 L/min
"Summer" mode
Heated floor mode
Circulation pump
Boiler specs
Efficiency92.9 %91.1 %
Combustion chamberclosed (turbocharged)closed (turbocharged)
Flue diameter
60/100 mm /80/80 for split flue/
60/100 mm
Inlet gas pressure20 mbar13 mbar
Max. gas consumption2.73 m³/h2.78 m³/h
Expansion vessel capacity6 L8 L
Expansion vessel pressure0.5 bar0.5 bar
Heat exchangercopper
Connections
Mains water intake1/2"
DHW flow1/2"
Gas supply3/4"
Central heating flow3/4"
Central heating return3/4"
Safety
Safety systems
gas pressure drop
water overheating
flame loss
draft control
power outage
water circulation failure
frost protection
gas pressure drop
water overheating
flame loss
draft control
power outage
water circulation failure
frost protection
More specs
Dimensions (HxWxD)730x400x299 mm730x400x317 mm
Weight33 kg33.5 kg
Added to E-Catalognovember 2010august 2010

Min. heat output

The minimum heat output at which the heating boiler can operate in constant mode. Operation at minimum power allows you to reduce the number of on-and-off cycles that adversely affect the durability of heating boilers.

Power consumption

The maximum electrical power consumed by the boiler during operation. For non-electric models (see Energy source), this power is usually low, as it is required mainly for control circuits and it can be ignored. Regarding electric boilers, it is worth noting that the power consumption in them is most often somewhat higher than the useful one since part of the energy is inevitably dissipated and not used for heating. Accordingly, the ratio of useful and consumed power can be used to evaluate the efficiency of such a boiler.

DHW max. T

The maximum temperature of domestic hot water supplied by a dual-circuit boiler. For comparison, we note that water begins to be perceived as warm, starting from 40 °C, and in centralized hot water supply systems, the temperature of hot water is usually about 60 °C (and should not exceed 75 °C). Accordingly, even in the most modest models, this figure is about 45 °C, in the vast majority of modern boilers, it is not lower than 50 °C, and in some models, it can even exceed 90 °C.

Also when heated to a given temperature, the temperature difference ("ΔT") may be different — depending on the initial temperature of the cold water. And the performance of the boiler in the DHW mode directly depends on ΔT; see below for performance details.

Performance (ΔT ~30 °C)

The performance of a dual-circuit boiler in hot water mode when water is heated by approximately 30 °C above the initial temperature.

Performance is the maximum amount of hot water the unit can produce in a minute. It depends not only on the power of the heater as such, but also on how much water needs to be heated: the higher the temperature difference ΔT between cold and heated water, the more energy is required for heating and the smaller the volume of water with which the boiler can handle in this mode. Therefore, the performance of dual-circuit boilers is indicated for certain ΔT — namely 25 °C, 30 °C and/or 50 °C. And it is worth choosing according to this indicator, taking into account the initial water temperature and taking into account what kind of hot water demand there is at the installation site of the boiler (how many points of water intake, what are the temperature requirements, etc.). Recommendations on this subject can be found in special sources.

We also recall that water begins to be felt by a person as warm somewhere from 40 °C, as hot — somewhere from 50 °C and the temperature of hot water in central water supply systems (according to official standards) is at least 60 °C. Thus, for the boiler to operate in the mode ΔT ~ 30 °C and give out at least warm water at 40 °C, the initial temperature of cold water should be about 10 °C (10 + 30=40 °C). A similar temperature can be found in wells in the warm season, and cold water in the ce...ntralized water supply system often warms up to 10 °C in the warm season. However, boilers, including dual-circuit boilers, are switched on mainly in cold weather, when the initial water temperature is noticeably lower. Accordingly, if the boiler is used as the main water heater, heating to the claimed temperatures (see "DHW min. T", "DHW max. T") often requires a greater ΔT than 30 °C, and the performance is less than indicated in this paragraph. But when operating in the preheating mode (when the water is heated to the desired temperature by an additional device like a boiler), this parameter describes the capabilities of the unit very reliably.

"Summer" mode

It is an operating mode designed for the warm season. In this mode, it works only to provide domestic hot water, and the heating is turned off. If the boiler is equipped with an outside temperature sensor, this sensor is also switched off in summer mode so that the heating does not turn on at night when the outside temperature drops.

Efficiency

The efficiency of the boiler.

For electric models (see "Energy source"), this parameter is calculated as the ratio of net power to consumed; in such models, indicators of 98 – 99% are not uncommon. For other boilers, the efficiency is the ratio of the amount of heat directly transferred to the water to the total heat amount released during combustion. In such devices, the efficiency is lower than in electric ones; for them, a parameter of more than 90% is considered good. An exception is gas condensing boilers (see the relevant paragraph), where the efficiency can even be higher than 100%. There is no violation of the laws of physics here. It is a kind of advertising trick: when calculating the efficiency, an inaccurate method is used that does not take into account the energy spent on the formation of water vapour. Nevertheless, formally everything is correct: the boiler gives out more thermal energy to the water than is released during the combustion of fuel since condensation energy is added to the combustion energy.

Inlet gas pressure

It is the optimum gas pressure supplied to the inlet of the boiler system. Most often indicated for natural gas and is about 15-20 mbar. This parameter must match the specs of the gas supply system. However, the pressure in the latter may be higher, which may require the installation of a special gas regulator.

Max. gas consumption

Maximum gas consumption in the boiler with the corresponding energy source (see above). Achieved when the gas heater is operating at full capacity; with reduced power and consumption, respectively, will be lower.

Note that boilers of the same power may differ in gas consumption due to the difference in efficiency. While the more fuel-efficient models tend to cost more, the price difference pays off in gas savings.

Expansion vessel capacity

The capacity of the expansion tank supplied with the boiler.

The expansion tank is designed to drain excess water from the heating system when the total volume of liquid increases as a result of heating. It consists of two parts connected by a flexible membrane: in one, hermetically closed, there is air under pressure; in the other, excess water enters, compressing the membrane. In this way, a catastrophic increase in pressure in the heating circuit is avoided. The optimal volume of the expansion tank depends on several system parameters, primarily the volume and composition of the coolant; detailed recommendations for calculations can be found in special sources.
BAXI Eco Four 24 F often compared