USA
Catalog   /   Home & Renovation   /   Electrical Equipment   /   Voltage Monitoring Relays

Comparison ADECS ADC-0111-40 vs ADECS ADC-0110-50

Add to comparison
ADECS ADC-0111-40
ADECS ADC-0110-50
ADECS ADC-0111-40ADECS ADC-0110-50
Outdated ProductOutdated Product
TOP sellers
Devicemultifunctional relaymultifunctional relay
Voltagevariablevariable
Number of phases11
MountdIN raildIN rail
Width (unit)3 U3 U
Specs
Power8.8 kVA11 kVA
Rated current40 А50 А
Maximum current50 А63 А
Voltage measuring range120 – 400 V120 – 400 V
Measurement accuracy (±)1 %1 %
Cut-off time (lower limit)0.01 с0.02 с
Off time (upper limit)0.01 с0.02 с
Reclosing delay10 – 990 с10 – 990 с
Lower cut-off limit150 – 195 V150 – 195 V
Upper cut-off limit245 – 270 V245 – 270 V
Current trip limit25, 32, 40 А32, 40, 50 А
Functions
display
thermal protection
fault memory
display
thermal protection
fault memory
General
Adjustmentdigitaldigital
Protection levelIP20IP20
Dimensions53x95x66 mm53x95x66 mm
Weight175 g155 g
Added to E-Catalogdecember 2017december 2017

Power

The rated power of the relay in kilovolt-amperes, in other words, the maximum apparent load power with which the device can normally operate.

From a physical point of view, kilovolt-amperes and kilowatts mean the same thing, but in kW it is customary to indicate only the active power of the load (see below), and in kVA — full. In AC networks, these powers can vary because active power (the power consumed by resistive-type devices such as heaters) is added to reactive power (the power consumed by capacitors and inductors). The apparent power is calculated from these two quantities.

When selecting control relays for AC networks, it is best to take into account the full power, especially if you plan to connect equipment with electric motors to the device. However, for many modern household appliances, only active power is given in the characteristics — in kilowatts. There are calculation methods that allow converting active power into total power, depending on the type and characteristics of the load; such techniques can be found in special sources.

Rated current

Rated switching current for which the control relay is set. In some models, this parameter can be changed at the request of the user; for such devices, the current value set in the factory settings is indicated (usually, this is the maximum indicator).

For a voltage relay (see “Device”), the rated current is the maximum current allowed for the device and the network segment protected by it for an unlimited time, in fact, the maximum current in normal operation. Exceeding this current is allowed, but not for long (up to several minutes) and not much, not higher than the maximum current (see below). And devices with the functions of a current relay or a power relay can work as follows: if the actual current is between the rated and maximum, the relay goes into the “delayed off” mode, and turns off the power after a certain period of time (for example, 10 minutes). This avoids both overload from long-term operation at high currents, and unnecessary power outages at large, but short-term permissible loads.

Maximum current

Maximum switching current allowed for the control relay. This is the maximum current that the device can safely pass through itself. And for models with current relay functions (see "Device"), this is also the default threshold of instantaneous operation — the current at which the relay instantly turns off the power to the load. In many models, you can set a lower threshold, but not a higher one.

Cut-off time (lower limit)

Time to turn off the device on the lower limit of voltage or current. This is a kind of "reaction time" of the relay: the period of time between reaching the lower limit and turning off the protected network segment.

The lower this value, the more advanced the protection will be, the lower the probability of failure of sensitive devices due to untimely operation of the relay. On the other hand, a high response rate for the lower limit is not as critical as for the upper one, and the shutdown time can be quite long — 1 s or more.

Also note that for some devices, this paragraph gives the minimum turn-off time (fastest response time), while in certain modes this time may be longer. For example, a voltage relay with a lower limit of 160 V may provide tripping after less than 0.05 s when the voltage drops below 120 V and tripping after 1 s when the voltage is in the range of 120 – 160 V, but above 120 V. This avoids unnecessary shutdowns with relatively weak and short-term voltage deviations. In the characteristics of such a device, 0.05 s will be indicated.

Off time (upper limit)

The device shutdown time on the upper limit of voltage or current. This is a kind of "reaction time" of the relay: the period of time between reaching the upper limit and turning off the protected network segment.

The lower this value, the more advanced the protection will be, the lower the probability of failure of sensitive devices due to untimely operation of the relay. Note that a short reaction time in this case is especially important, because too high a voltage or current is a serious danger to any device.

Current trip limit

The upper current shutdown limit provided in the device is the threshold above which the relay switches off the protected network segment. Many models allow you to adjust this limit; for them, the range of such adjustment is indicated in the characteristics. Note that for the upper limit of this range, some manufacturers take not the maximum, but the rated current of the device; see above for details on these options.