USA
Catalog   /   Climate, Heating, Water Heating   /   Heating & Boilers   /   Boilers

Comparison Bosch Gaz 6000 WBN-24C RN 24 kW vs Hermann HABITAT 2 23E 23 kW

Add to comparison
Bosch Gaz 6000 WBN-24C RN 24 kW
Hermann HABITAT 2 23E 23 kW
Bosch Gaz 6000 WBN-24C RN 24 kWHermann HABITAT 2 23E 23 kW
from $536.40 up to $709.58
Outdated Product
from $621.00
Outdated Product
TOP sellers
Main
DHW capacity at Δt=30° - 11.4 L/min, at Δt=50° - 6.8 L/min. Light weight. Frost protection. Resistant to mains voltage fluctuations. Ability to work with liquefied gas.
Energy sourcegasgas
Installationwallwall
Typedual-circuit (heating and DHW)dual-circuit (heating and DHW)
Heating area192 m²172 m²
Technical specs
Heat output24 kW23 kW
Min. heat output7.2 kW
Power supply230 V230 V
Power consumption110 W
Coolant min. T40 °С35 °С
Coolant max. T82 °С78 °С
Heating circuit max. pressure3 bar3 bar
DHW circuit max. pressure10 bar
Consumer specs
DHW min. T35 °С30 °С
DHW max. T60 °С55 °С
Performance (ΔT=25°C)13.3 L/min
Performance (ΔT ~30 °C)11.1 L/min
"Summer" mode
Heated floor mode
Circulation pump
Control busOpenTherm
Boiler specs
Efficiency93.2 %90.4 %
Combustion chamberclosed (turbocharged)open (atmospheric)
Flue diameter
60/100 mm /80/80 mm for separate/
Inlet gas pressure16 mbar20 mbar
Max. gas consumption2.8 m³/h2.71 m³/h
Expansion vessel capacity8 L8 L
Expansion vessel pressure0.5 bar
Heat exchangercopper
Connections
Mains water intake1/2"1/2"
DHW flow1/2"1/2"
Gas supply3/4"3/4"
Central heating flow3/4"3/4"
Central heating return3/4"3/4"
Safety
Safety systems
gas pressure drop
water overheating
flame loss
draft control
 
water circulation failure
frost protection
gas pressure drop
water overheating
flame loss
draft control
power outage
 
frost protection
More specs
Dimensions (HxWxD)700x400x299 mm700x400x300 mm
Weight31 kg29 kg
Added to E-Catalogaugust 2014september 2010

Heating area

A very conditional parameter that slightly characterizes the purpose based on the size of the room. And depending on the height of the ceilings, layout, building design and equipment, actual values may differ significantly. However, this item represents the maximum recommended area of the room that the boiler can effectively heat. However, it is worth considering that different buildings have different thermal insulation properties and modern buildings are much “warmer” than 30-year-old and especially 50-year-old houses. Accordingly, this item is more of a reference nature and does not allow us to fully assess the actual heated area. There is a formula by which you can derive the maximum heating area, knowing the useful power of the boiler and the climatic conditions in which it will be used; For more information on this, see "Useful Power". In our case, the heating area is calculated using the formula “boiler power multiplied by 8”, which is approximately equivalent to use in houses that are several decades old.

Heat output

It is the maximum useful power of the boiler.

The ability of the device to heat a room of a particular area directly depends on this parameter; by power, you can approximately determine the heating area, if this parameter is not indicated in the specs. The most general rule says that for a dwelling with a ceiling height of 2.5 – 3 m, at least 100 W of heat power is needed to heat 1 m2 of area. There are also more detailed calculation methods that take into account specific factors: the climatic zone, heat gain from the outside, design features of the heating system, etc.; they are described in detail in special sources. Also note that in dual-circuit boilers (see "Type"), part of the heat generated is used to heat water for the hot water supply; this must be taken into account when evaluating the output power.

It is believed that boilers with a power of more than 30 kW must be installed in separate rooms (boiler rooms).

Min. heat output

The minimum heat output at which the heating boiler can operate in constant mode. Operation at minimum power allows you to reduce the number of on-and-off cycles that adversely affect the durability of heating boilers.

Power consumption

The maximum electrical power consumed by the boiler during operation. For non-electric models (see Energy source), this power is usually low, as it is required mainly for control circuits and it can be ignored. Regarding electric boilers, it is worth noting that the power consumption in them is most often somewhat higher than the useful one since part of the energy is inevitably dissipated and not used for heating. Accordingly, the ratio of useful and consumed power can be used to evaluate the efficiency of such a boiler.

Coolant min. T

The minimum operating temperature of the heat medium in the boiler system when operating in heating mode.

Coolant max. T

The maximum operating temperature of the heat medium in the boiler system when operating in heating mode.

DHW circuit max. pressure

The maximum pressure in the hot water circuit (DHW) at which it can operate for a long time without failures and damage. See "Heating circuit maximum pressure".

DHW min. T

The minimum temperature of domestic hot water (DHW) supplied by a dual-circuit boiler. For comparison, we note that water begins to be perceived as warm, starting from 40 °C, and in centralized hot water supply systems, the temperature of hot water is usually about 60 °C (and should not exceed 75 °C). At the same time, in some boilers, the minimum heating temperature can be only 10 °C or even 5 °C. A similar mode of operation is used to protect pipes from freezing during the cold season: the circulation of water with a positive temperature prevents the formation of ice inside and damage to the circuits.

It is also worth keeping in mind that when heated to a given temperature, the temperature difference ("ΔT") may be different — depending on the initial temperature of the cold water. And the performance of the boiler in the DHW mode directly depends on ΔT; see below for performance details.

DHW max. T

The maximum temperature of domestic hot water supplied by a dual-circuit boiler. For comparison, we note that water begins to be perceived as warm, starting from 40 °C, and in centralized hot water supply systems, the temperature of hot water is usually about 60 °C (and should not exceed 75 °C). Accordingly, even in the most modest models, this figure is about 45 °C, in the vast majority of modern boilers, it is not lower than 50 °C, and in some models, it can even exceed 90 °C.

Also when heated to a given temperature, the temperature difference ("ΔT") may be different — depending on the initial temperature of the cold water. And the performance of the boiler in the DHW mode directly depends on ΔT; see below for performance details.
Bosch Gaz 6000 WBN-24C RN often compared
Hermann HABITAT 2 23E often compared