USA
Catalog   /   Home & Renovation   /   Electrical Equipment   /   UPS

Comparison Mustek PowerMust 800 Sinewave LCD 800-LCD-LIS-T10 800 VA vs RITAR RTSW-800D12 800 VA

Add to comparison
Mustek PowerMust 800 Sinewave LCD 800-LCD-LIS-T10 800 VA
RITAR RTSW-800D12 800 VA
Mustek PowerMust 800 Sinewave LCD 800-LCD-LIS-T10 800 VARITAR RTSW-800D12 800 VA
Outdated Product
from $100.00 up to $125.28
Outdated Product
TOP sellers
Typesmartsmart
Form factorstandard (Tower)standard (Tower)
Switching to battery6 ms6 ms
Input
Input voltage1 phase (230V)1 phase (230V)
Input voltage range162 – 290 V175 – 270 V
Max. current6 A
Input frequency49 – 61 Hz50/60 Hz
Bypass (direct connection)is absentis absent
Output
Output voltage1 phase (230V)1 phase (230V)
Max. output power800 VA800 VA
Rated output power480 W480 W
Output waveformsinusoid (PSW)sinusoid (PSW)
Output frequency49 – 61 Hz50/60 Hz
Redundant sockets22
Socket typetype F (Schuko)type F (Schuko)
Battery
No included battery
Battery connection voltage12 V
Supplied battery(s) capacity9 Ah
Batteries1
Full charge time360 min
Cold start
External battery connection
Protection
Protection
short circuit protection
overload protection
noise filtering
data line protection
sound alarm
short circuit protection
overload protection
noise filtering
 
sound alarm
Fuseautoauto
Control interfaces
 
USB
RS-232
 
General
Screen
Operating temperature0 – 40 °C0 – 45 °C
Noise level40 dB45 dB
Dimensions (HxWxD)145x100x328 mm220x145x405 mm
Weight6 kg6.8 kg
Added to E-Catalogaugust 2019november 2016

Input voltage range

In this case, the input voltage range is implied, in which the UPS is able to supply a stable voltage to the load only due to its own regulators, without switching to the battery. For redundant UPSs (see "Type") this range is quite small, approximately 190 to 260 V; for interactive and especially inverter ones, it is much wider. Some UPS models allow you to manually set the input voltage range.

Max. current

The maximum current drawn by the UPS. In fact, the current reaches its maximum value only when the UPS is operating from the mains with maximum load power and a completely discharged battery. However, when calculating the load on the power grid, this parameter should be taken into account.

Input frequency

The operating frequency of the alternating current supplied to the input of the UPS — or more precisely, the frequency range of this current in which the device can supply the required power to the load due to its own regulators, without using a battery. When this range is exceeded, the UPS switches to battery mode. The smallest input voltage range is reserved for standby UPSs (see "Type"), the largest for inverter UPSs.

Output frequency

The frequency (frequency range) of the AC voltage output by the UPS. For computer technology, the frequency range of 47-53 Hz is considered normal, although the smaller the deviation from the 50 Hz standard, the better. On the other hand, in some UPS models, this frequency can be automatically synchronized with the frequency of the mains — so the power supplied to the load will not differ regardless of whether the load is powered by the mains or from the battery. In this case, a wider frequency range, on the contrary, is more desirable.

No included battery

The absence of a battery in the UPS package — in order to use such a device for its main purpose, the battery will have to be purchased separately. This is associated with additional hassle, but gives such an important advantage as the ability to independently choose the capacity and number of batteries, without relying on the choice of the manufacturer and without the risk of overpaying for the wrong option.

Note that only models that do not have internal batteries and are designed to use external batteries can be supplied in this configuration (see below). These can be both professional inverter models (see "Type"), and inexpensive backup ones.

Battery connection voltage

Rated voltage of external batteries that can be used in the UPS.

For more information about such batteries, see " Connecting an external battery ", here it is worth saying that the voltage of the external battery must correspond to the voltage for which the "uninterruptible" is designed. If these parameters differ, at best, the UPS simply “will not start”, and at worst, overloads and even a fire are possible.

In general, the more powerful the UPS, the higher, usually, the voltage of the external batteries for which it is designed. However, there is no hard dependency here. And some models even allow several voltage options, for example 96/108/120 V. Also note that a battery with the required voltage can be assembled from several batteries with a lower number of volts connected in series: for example, for 36 V, you can use 3 batteries of 12 AT.

Separately, it is worth emphasizing that the standard voltages for most modern uninterruptible power supplies are multiples of 12 V, however, car batteries cannot be used in such devices. Despite the identical voltage, such batteries are designed for a fundamentally different format of operation, and their use in a UPS is fraught with, at best, incorrect operation of the device, and at worst, fires and even explosions.

Supplied battery(s) capacity

The capacity of the battery installed in the UPS. For models with multiple batteries, this is both the total working capacity and the capacity of each individual battery: the batteries in such devices are usually connected in series, so that their total capacity corresponds to the capacity of each individual cell.

Theoretically, a higher battery capacity means the ability to power loads of a given capacity for longer. However, in fact, this parameter is more of a reference than practically significant. The fact is that the actual amount of energy stored by the battery depends not only on the capacity in amp-hours, but also on the voltage in volts; this voltage is often not specified in the characteristics, despite the fact that for accurate calculations it must be known. So when choosing, you should focus on more "close to life" characteristics — first of all, on the directly claimed operating time in different modes (see above).

Batteries

The number of batteries supplied with the UPS.

In general, this parameter is more of a reference than practically significant: the number of batteries is selected in such a way as to provide the desired performance — primarily the time of continuous operation. First of all, it is worth paying attention to such characteristics when choosing.

Full charge time

The time it takes to fully charge the UPS battery. Note that in this case, this time is calculated according to special rules: not from 0 to 100% of the charge, but from a state in which it is impossible to maintain half the load, up to 90% of the charge. Of course, a full charge will take a little longer. However, this data is closer to practice than the “from 0 to 100%” calculation: the inability to work at half load makes the UPS practically useless, and this condition can be taken as zero, and 90% of the battery is already able to provide a good guarantee in case of a power failure.