USA
Catalog   /   Home & Renovation   /   Electrical Equipment   /   Voltage Monitoring Relays

Comparison DigiTOP MP-63A vs DigiTOP VP-16A

Add to comparison
DigiTOP MP-63A
DigiTOP VP-16A
DigiTOP MP-63ADigiTOP VP-16A
Outdated ProductOutdated Product
TOP sellers
Devicemultifunctional relayvoltage Monitoring Relays
Voltagevariablevariable
Number of phases11
MountdIN raildIN rail
Width (unit)3 U2 U
Specs
Power2.2 kVA
Rated current63 A10 A
Maximum current70 A16 A
Voltage measuring range100 – 400 V100 – 400 V
Measurement accuracy (±)1 %2.2 %
Cut-off time (lower limit)0.06 sec0.02 sec
Off time (upper limit)0.06 sec0.02 sec
Reclosing delay5 – 600 sec5 – 600 sec
Lower cut-off limit120 – 200 V120 – 200 V
Upper cut-off limit210 – 270 V210 – 270 V
Current trip limit1 – 63 A
Functions
display
display
General
Adjustmentdigitaldigital
Protection levelIP20IP20
Added to E-Catalogdecember 2017december 2017

Device

— Voltage relay. Protective devices that automatically turn off the protected area when the mains voltage goes beyond the specified parameters. Usually, such devices are able to respond to both a significant increase and a significant decrease in voltage. A voltage relay will be a useful addition to traditional protection such as plugs or a circuit breaker, since such protection only reacts to excess current and does not monitor voltage. And in three-phase networks, protective relays can also provide monitoring of phase synchronization, triggering in case of skew, breakage, sticking or phase sequence violation.

Current relay. Protective devices that automatically turn off the protected area when the consumed current exceeds the specified parameters. It is similar in purpose to circuit breakers, however, firstly, the current relays can also respond to a decrease in current, and secondly, such a device may not work instantly, but after a certain time. It makes sense to install a current relay where short-term operation at high currents is allowed, however, the time of this operation must be limited, and also where long-term idle operation at low currents is undesirable. A classic example is connecting a power-controlled motor: the current at maximum power can be set as an upper limit, and the lower limit can be set just above the no-load current. The shutdown time in such devices, usually, can be set within a few minutes.
...> — Power relay. Protective devices that automatically turn off the protected section of the circuit when the power consumption is exceeded. Such a device monitors both the current strength and the voltage at the same time — we recall that the power is calculated by the formula "current strength multiplied by voltage." The need for a power relay is due to the fact that in some situations it is not an excess of current or voltage that gives an overload, but a combination of them — moreover, both volts and amperes can remain within acceptable values.

Multifunctional relay. Models that combine the capabilities of several protective devices. A multifunctional device usually has the function of a voltage relay (with upper and lower trip limits) and a power relay or current relay (both with only an upper limit). See above for details of each variety; here we note that their multifunctional relay allows you to get by with one device instead of two.

Phase selection relay. Protective devices used when supplying a single-phase load through a three-phase network. As the name suggests, such a relay provides automatic selection of the most favorable phase; in other words, if a failure occurs on the current phase, the device switches the load to another phase, with more stable voltage indicators. Such devices are mainly intended for connecting especially important and sensitive devices that have increased requirements for voltage stability.

Impulse relay. Control devices that close or open the circuit when a short-term voltage pulse is applied to the control input. Also, such devices are called bistable, since each of the switch positions (both “on” and “off”) is stable and changes only when a control pulse is received. One of the options for using such relays is to control lighting from several places at the same time, for example, from two switches installed at different ends of a long corridor. By connecting both of these switches to an impulse relay, one can turn on the light at the entrance to the corridor, and the second one can turn it off at the exit, regardless of the direction of movement. Theoretically, even on one relay, you can tie up as many switches as you like; there are more complex schemes for the use of bistable control devices.

Width (unit)

Width expressed in unit units. This unit is used to measure the width of rack-mounted devices and makes it easy to estimate how much space you need. Width in unit is always expressed as whole numbers, 1 unit is approximately equal to 17.5 mm. There are models 1U, 2U, 3U and more

Power

The rated power of the relay in kilovolt-amperes, in other words, the maximum apparent load power with which the device can normally operate.

From a physical point of view, kilovolt-amperes and kilowatts mean the same thing, but in kW it is customary to indicate only the active power of the load (see below), and in kVA — full. In AC networks, these powers can vary because active power (the power consumed by resistive-type devices such as heaters) is added to reactive power (the power consumed by capacitors and inductors). The apparent power is calculated from these two quantities.

When selecting control relays for AC networks, it is best to take into account the full power, especially if you plan to connect equipment with electric motors to the device. However, for many modern household appliances, only active power is given in the characteristics — in kilowatts. There are calculation methods that allow converting active power into total power, depending on the type and characteristics of the load; such techniques can be found in special sources.

Rated current

Rated switching current for which the control relay is set. In some models, this parameter can be changed at the request of the user; for such devices, the current value set in the factory settings is indicated (usually, this is the maximum indicator).

For a voltage relay (see “Device”), the rated current is the maximum current allowed for the device and the network segment protected by it for an unlimited time, in fact, the maximum current in normal operation. Exceeding this current is allowed, but not for long (up to several minutes) and not much, not higher than the maximum current (see below). And devices with the functions of a current relay or a power relay can work as follows: if the actual current is between the rated and maximum, the relay goes into the “delayed off” mode, and turns off the power after a certain period of time (for example, 10 minutes). This avoids both overload from long-term operation at high currents, and unnecessary power outages at large, but short-term permissible loads.

Maximum current

Maximum switching current allowed for the control relay. This is the maximum current that the device can safely pass through itself. And for models with current relay functions (see "Device"), this is also the default threshold of instantaneous operation — the current at which the relay instantly turns off the power to the load. In many models, you can set a lower threshold, but not a higher one.

Measurement accuracy (±)

Measurement accuracy provided by the device. In this case, different types of measurements may be implied, depending on the purpose of the relay (see "Device"). Note that in power relays and multifunctional devices, the measurement accuracy for voltage and current is usually the same, and a common parameter is given in the characteristics for them.

Accuracy is indicated by the maximum measurement error provided by the device. First of all, the operation accuracy depends on this parameter: the lower the error, the smaller the actual deviations from the specified operation parameters. For modern control relays, an indicator of 3 – 5% is considered acceptable, 1.5 – 3% is not bad, 1 – 1.5% is good, less than 1% is excellent. However, in fact, it is also worth choosing according to this parameter, taking into account how sensitive the connected load is to the accuracy of the specified operation parameters.

Also note that many modern relays are equipped with digital displays that can display various parameters. In such models, the measurement accuracy also determines the accuracy of the readings of such a built-in "tester".

Cut-off time (lower limit)

Time to turn off the device on the lower limit of voltage or current. This is a kind of "reaction time" of the relay: the period of time between reaching the lower limit and turning off the protected network segment.

The lower this value, the more advanced the protection will be, the lower the probability of failure of sensitive devices due to untimely operation of the relay. On the other hand, a high response rate for the lower limit is not as critical as for the upper one, and the shutdown time can be quite long — 1 s or more.

Also note that for some devices, this paragraph gives the minimum turn-off time (fastest response time), while in certain modes this time may be longer. For example, a voltage relay with a lower limit of 160 V may provide tripping after less than 0.05 s when the voltage drops below 120 V and tripping after 1 s when the voltage is in the range of 120 – 160 V, but above 120 V. This avoids unnecessary shutdowns with relatively weak and short-term voltage deviations. In the characteristics of such a device, 0.05 s will be indicated.

Off time (upper limit)

The device shutdown time on the upper limit of voltage or current. This is a kind of "reaction time" of the relay: the period of time between reaching the upper limit and turning off the protected network segment.

The lower this value, the more advanced the protection will be, the lower the probability of failure of sensitive devices due to untimely operation of the relay. Note that a short reaction time in this case is especially important, because too high a voltage or current is a serious danger to any device.

Current trip limit

The upper current shutdown limit provided in the device is the threshold above which the relay switches off the protected network segment. Many models allow you to adjust this limit; for them, the range of such adjustment is indicated in the characteristics. Note that for the upper limit of this range, some manufacturers take not the maximum, but the rated current of the device; see above for details on these options.
DigiTOP MP-63A often compared