Comparison Zubr D6-50 red vs Zubr D40
Add to comparison | ![]() | ![]() |
|---|---|---|
| Zubr D6-50 red | Zubr D40 | |
| Outdated Product | Outdated Product | |
| User reviews | ||
| TOP sellers | ||
| Device | voltage Monitoring Relays | voltage Monitoring Relays |
| Voltage | variable | variable |
| Number of phases | 3 | 1 |
| Mount | dIN rail | dIN rail |
| Width (unit) | 6 U | 3 U |
Specs | ||
| Power | 11 kVA | 8.8 kVA |
| Rated current | 50 А | 40 А |
| Maximum current | 60 А | 50 А |
| Voltage measuring range | 100 – 420 В | 100 – 400 В |
| Cut-off time (lower limit) | 0.04 с | 1.2 с |
| Off time (upper limit) | 0.04 с | 0.04 с |
| Response time adjustment | ||
| Reclosing delay | 3 – 600 с | 3 – 600 с |
| Lower cut-off limit | 120 – 210 В | 120 – 210 В |
| Upper cut-off limit | 220 – 280 В | 220 – 280 В |
| Functions | display operation indicator thermal protection fault memory | display operation indicator fault memory |
General | ||
| Adjustment | digital | digital |
| Protection level | IP20 | IP20 |
| Dimensions | 106x85x66 mm | 70x85x53 mm |
| Weight | 430 g | 210 g |
| Added to E-Catalog | november 2023 | december 2017 |
Compare Zubr D6-50 red and D40
You may be interested in
My comparisons
Zubr D6-50 red often compared
Zubr D40 often compared
Glossary
Number of phases
The number of phases for which the relay is designed.
— 1. Single-phase power is known to everyone from classic 230 V household sockets. Actually, some relays for this voltage are even made in the form of socket adapters (see "Installation"). However, models are also produced for other values of alternating voltages — for example, 110 V.
— 3. Three-phase 400 V power supply is used mainly for high consumption devices for which 230 V networks do not provide enough power. Also note that switchboards in private houses are often connected to a three-phase electrical network, with further power distribution for individual phases. However, in such cases, it is more reasonable to use three separate relays for each of the phases, and not one three-phase device: in the first case, only part of the home network will lose power in the event of a power failure, in the second, the entire network.
— 1/3. A specific variant used exclusively in the phase selection relay. Such models take three phases as input, and only one is fed to the load; see "Device" for details.
— 1. Single-phase power is known to everyone from classic 230 V household sockets. Actually, some relays for this voltage are even made in the form of socket adapters (see "Installation"). However, models are also produced for other values of alternating voltages — for example, 110 V.
— 3. Three-phase 400 V power supply is used mainly for high consumption devices for which 230 V networks do not provide enough power. Also note that switchboards in private houses are often connected to a three-phase electrical network, with further power distribution for individual phases. However, in such cases, it is more reasonable to use three separate relays for each of the phases, and not one three-phase device: in the first case, only part of the home network will lose power in the event of a power failure, in the second, the entire network.
— 1/3. A specific variant used exclusively in the phase selection relay. Such models take three phases as input, and only one is fed to the load; see "Device" for details.
Width (unit)
Width expressed in unit units. This unit is used to measure the width of rack-mounted devices and makes it easy to estimate how much space you need. Width in unit is always expressed as whole numbers, 1 unit is approximately equal to 17.5 mm. There are models 1U, 2U, 3U and more
Power
The rated power of the relay in kilovolt-amperes, in other words, the maximum apparent load power with which the device can normally operate.
From a physical point of view, kilovolt-amperes and kilowatts mean the same thing, but in kW it is customary to indicate only the active power of the load (see below), and in kVA — full. In AC networks, these powers can vary because active power (the power consumed by resistive-type devices such as heaters) is added to reactive power (the power consumed by capacitors and inductors). The apparent power is calculated from these two quantities.
When selecting control relays for AC networks, it is best to take into account the full power, especially if you plan to connect equipment with electric motors to the device. However, for many modern household appliances, only active power is given in the characteristics — in kilowatts. There are calculation methods that allow converting active power into total power, depending on the type and characteristics of the load; such techniques can be found in special sources.
From a physical point of view, kilovolt-amperes and kilowatts mean the same thing, but in kW it is customary to indicate only the active power of the load (see below), and in kVA — full. In AC networks, these powers can vary because active power (the power consumed by resistive-type devices such as heaters) is added to reactive power (the power consumed by capacitors and inductors). The apparent power is calculated from these two quantities.
When selecting control relays for AC networks, it is best to take into account the full power, especially if you plan to connect equipment with electric motors to the device. However, for many modern household appliances, only active power is given in the characteristics — in kilowatts. There are calculation methods that allow converting active power into total power, depending on the type and characteristics of the load; such techniques can be found in special sources.
Rated current
Rated switching current for which the control relay is set. In some models, this parameter can be changed at the request of the user; for such devices, the current value set in the factory settings is indicated (usually, this is the maximum indicator).
For a voltage relay (see “Device”), the rated current is the maximum current allowed for the device and the network segment protected by it for an unlimited time, in fact, the maximum current in normal operation. Exceeding this current is allowed, but not for long (up to several minutes) and not much, not higher than the maximum current (see below). And devices with the functions of a current relay or a power relay can work as follows: if the actual current is between the rated and maximum, the relay goes into the “delayed off” mode, and turns off the power after a certain period of time (for example, 10 minutes). This avoids both overload from long-term operation at high currents, and unnecessary power outages at large, but short-term permissible loads.
For a voltage relay (see “Device”), the rated current is the maximum current allowed for the device and the network segment protected by it for an unlimited time, in fact, the maximum current in normal operation. Exceeding this current is allowed, but not for long (up to several minutes) and not much, not higher than the maximum current (see below). And devices with the functions of a current relay or a power relay can work as follows: if the actual current is between the rated and maximum, the relay goes into the “delayed off” mode, and turns off the power after a certain period of time (for example, 10 minutes). This avoids both overload from long-term operation at high currents, and unnecessary power outages at large, but short-term permissible loads.
Maximum current
Maximum switched current allowed for the control relay. This is the highest current that the device can safely pass through itself. And for models with current relay functions (see "Device"), this is also the default instantaneous trip threshold — the current at which the relay instantly cuts off power to the load. In many models, a lower trip threshold can be set, but not a higher one.
Voltage measuring range
Voltage measurement range supported by the device.
Many modern control relays are equipped with digital displays, which can display, including current voltage; this parameter specifies the operating range of the built-in voltmeter. In this case, the voltage measurement range can be noticeably wider than the difference between the smallest minimum and the largest maximum shutdown threshold (see below). This allows you to use the relay also for online diagnostics of the network status.
For a current relay (see "Device") in this case, the range of operating voltages can be given directly — the voltage at which the device can normally perform its functions.
Many modern control relays are equipped with digital displays, which can display, including current voltage; this parameter specifies the operating range of the built-in voltmeter. In this case, the voltage measurement range can be noticeably wider than the difference between the smallest minimum and the largest maximum shutdown threshold (see below). This allows you to use the relay also for online diagnostics of the network status.
For a current relay (see "Device") in this case, the range of operating voltages can be given directly — the voltage at which the device can normally perform its functions.
Cut-off time (lower limit)
Time to turn off the device on the lower limit of voltage or current. This is a kind of "reaction time" of the relay: the period of time between reaching the lower limit and turning off the protected network segment.
The lower this value, the more advanced the protection will be, the lower the probability of failure of sensitive devices due to untimely operation of the relay. On the other hand, a high response rate for the lower limit is not as critical as for the upper one, and the shutdown time can be quite long — 1 s or more.
Also note that for some devices, this paragraph gives the minimum turn-off time (fastest response time), while in certain modes this time may be longer. For example, a voltage relay with a lower limit of 160 V may provide tripping after less than 0.05 s when the voltage drops below 120 V and tripping after 1 s when the voltage is in the range of 120 – 160 V, but above 120 V. This avoids unnecessary shutdowns with relatively weak and short-term voltage deviations. In the characteristics of such a device, 0.05 s will be indicated.
The lower this value, the more advanced the protection will be, the lower the probability of failure of sensitive devices due to untimely operation of the relay. On the other hand, a high response rate for the lower limit is not as critical as for the upper one, and the shutdown time can be quite long — 1 s or more.
Also note that for some devices, this paragraph gives the minimum turn-off time (fastest response time), while in certain modes this time may be longer. For example, a voltage relay with a lower limit of 160 V may provide tripping after less than 0.05 s when the voltage drops below 120 V and tripping after 1 s when the voltage is in the range of 120 – 160 V, but above 120 V. This avoids unnecessary shutdowns with relatively weak and short-term voltage deviations. In the characteristics of such a device, 0.05 s will be indicated.
Response time adjustment
Delay time adjustment means that after detecting a fault (voltage dip/surge, current overload, power overdraw), the device doesn't immediately break the circuit, but does so after an adjustable delay. This adjustment filters out short-lived surges and drops, eliminating false triggers from motor starting currents and stabilizing the operation of lines with a generator or unstable network. Typically, the range is from fractions of a second to tens of seconds or minutes; for electronics, minimal values are chosen, while for compressors and pumps, larger values are preferred. Compared to "instant" relays, models with delay time adjustment provide more control and fewer downtimes, but require proper setup along with thresholds and delay for reconnection. Example: a refrigerator or heat pump can withstand a brief spike, but with a prolonged deviation, the relay safely disconnects the load and logs the event.
Functions
— Display. As a rule, control relays are equipped with simple segment LCD displays that can display numbers and some special characters. This screen performs two main functions. Firstly, during operation it displays key network parameters - voltage, power and/or power, as well as notifications of problems; Some models provide several separate displays, each with its own parameter. Secondly, the screen is used when changing device settings.
— Operation indicator. A pointer indicating the operation of a device, and often a specific mode of operation. Note that in this case we are talking about the simplest indicators - for example, in the form of an LED, which lights up green in normal mode and lights up red after the protection is triggered. The display is not considered an operation indicator, although it can perform such a function.
— Thermal protection. A safety system that turns off the device when it reaches a critical temperature. Some models also provide a shutdown when the permissible heating rate is exceeded. This function serves as additional insurance in case of malfunctions in the relay itself (for example, if the settings are lost and the device does not respond to overload), and in case of fire (in case of fire, the equipment must be de-energized).
— Memory of emergency operations. The function...of saving data on the state of the network during emergencies. Allows you to assess the situation of what happened after resuming work.
— Operation indicator. A pointer indicating the operation of a device, and often a specific mode of operation. Note that in this case we are talking about the simplest indicators - for example, in the form of an LED, which lights up green in normal mode and lights up red after the protection is triggered. The display is not considered an operation indicator, although it can perform such a function.
— Thermal protection. A safety system that turns off the device when it reaches a critical temperature. Some models also provide a shutdown when the permissible heating rate is exceeded. This function serves as additional insurance in case of malfunctions in the relay itself (for example, if the settings are lost and the device does not respond to overload), and in case of fire (in case of fire, the equipment must be de-energized).
— Memory of emergency operations. The function...of saving data on the state of the network during emergencies. Allows you to assess the situation of what happened after resuming work.